OUNEVA OY PRODUCT CATALOG 2018
Universal connectors
OTL 1000 V
Five reasons to choose OTL 1000 V
Criteria Conditions 94V-0 94V-1 94V-2
Total aming combustion for each specimen ≤ 10 sec ≤ 30 sec ≤ 30 sec
Total aming combustion for all 5 specimens of any set ≤ 50 sec ≤ 250 sec ≤ 250 sec
Flaming and glowing combustion for each specimen after second burner ame application ≤ 30 sec ≤ 60 sec ≤ 60 sec
Cotton ignited by aming drips from any specimen No No Yes
Material classication according to UL 94 standard (vertical burning test)
Certication and product safety
When choosing electrical connector, always make sure to select
reliable and safe, certied connector. The requirements for connectors
used with copper conductors inside switchgears and similar
appliances are specied in standard EN 60947-7-1:2009.
All connectors used inside switchgears or similar appliances must
full these requirements.
The requirements for connectors designated to be used with
aluminium power cables are specied in standard EN 61238-1:2003.
Connectors that have been tested and certied in accordance with
standard EN 61238-1:2003 are divided into two classes.
• Class A (short circuit tested) - usage examples:
feed-in connections, switchgears/appliances, universal
• Class B (not short circuit tested) - usage limited
only to special circuits protected by fast-acting fuses
Ouneva OTL-connectors are tested and certied class A connectors,
that are compatible with copper and aluminium conductors.
For choosing safe and reliable connector, always make sure that the
terminal is equipped with CE and Class A markings with the symbol
of certifying institute, for example FI -mark.
General/use: New OTL 1000 V connector series offers the best quality,
safety and installation features on the market. OTL-connectors are
designed to be used when connecting and branching aluminium and
copper cables.
Materials: Bodies of the connectors are made of aluminium and plated
with tin. Insulating covers are made of UL 94 V-0 class polyamide.
Certification and applied regulations:
EN 60947-7-1:2009, EN 61238-1:2003
Higher 1000 V
AC/DC voltage
rating
1
Tightening torque
labels on the
connector cover
2
Safe UL 94 V-0
class plastic
material
4
Easier installation
with conductor
input collars
3
Places for
component
markers
(5 mm width
eg. Partex Tx)
5
Product documents