Instruction Manual

6
BSelect the Proper Heating Cable Length
Use the following table to select the proper heating cable. (length)
Pipe
Length
Pipe Diameter
1/2” 3/4” 1” 1.25” 1.5”
3’ 3 3 3 3 3
4’
3
3 3 3 + 3 3 + 3
5’ 3 3 3 + 3 3 + 3 3 + 3
6’ 6 6 6 6 6
7’ 6 6 6 3 + 6 3 + 6
8’ 6 6 6 3 + 6 3 + 6
9’ 9 9 9 9 9
10’ 9 9 9 9 6 + 6
11’ 9 9 9 6 + 6 6 + 6
12’ 12 12 12 12 12
13’ 12 12 12 12 6 + 9
14’ 12 12 12 6 + 9 6 + 9
15’ 15 15 15 15 15
16’ 15 15 15 15 9 + 9
17’ 15 15 15 9 + 9 9 + 9
18’ 18 18 18 18 18
20’ 18 18 18 18 9 + 12
22’ 12 + 12
12 + 12
12 + 12 12 + 12 12 + 12
24’ 24 24 24 24 24
26’ 24 24 24 12 + 15 12 + 15
28’ 12 +15
12 +15
12 +15 12 + 15 12 + 18
30’ 30 30 30 30 30
35’
18 + 18
18 + 18
18 + 18
18 + 18
40’ 40 40 40 40 40
45’ 18 + 24
18 + 24
18 + 24 18 + 24 24 + 24
50’ 24 + 24
24 + 24
24 + 24 24 + 24 12 + 40
55’
24 + 30
24 + 30
24 + 30
18 + 40
60’
60
60
60
60
65’
6 + 60
6 + 60
6 + 60
6 + 60
70’ 30 + 40
30 + 40
30 + 40 30 + 40 12 + 60
75’ 15 + 60
15 + 60
15 + 60 15 + 60 15 + 60
80’
80
80
80
80
85’
24 +60
24 + 60
24 + 60
6 + 80
90’
30 + 60
30 + 60
30 + 60
30 + 60
95’ 18 +80
18 + 80
18 + 80 18 + 80 18 + 80
100’ 40 + 60
40 + 60
40 + 60 40 + 60 40 + 60
Example:
3 means: you need one 3’ heating cable.
3+3 means: you need two 3’ heating cables.
12+15 means: you need one 12’ heating
cable with one 15’ heating cable.
For pipe sizes not listed or for more
information, contact the factory
representative, please contact us.
This design guide is based on the generally
accepted maintenance temperature 4°C
(40°F) for freeze protection.
This design guide is calculated based on 0.5”
fiberglass insulation. Closed-cell flexible
foam insulation may also be used. If the
overall R value of the insulation, protective
barrier and waterproof barrier is not greater
than 2.0.