User's Manual
CHAPTER3
Performingconnectivitychecks
51
• 18 — attempt to insert a reserved device ID number (0 or 65535)
Realtimeclock
• 20 — incorrect time supplied (no conversion to time_t was
possible)
Radiointerface(includingGSM/GPRSModem)
• 30 — error at receive (CRC, etc.)
• 31 — unexpected frame received
• 32 — wrong length
• 33 — reserved
• 34 — reserved
• 35 — time-out (remote device not responding)
• 36 — receiver busy (for example, currently performing a polling
series)
• 37 — time stamp of a frame is too far in the future
• 38 — general modem error
• 39 — “unknown modem” error
Notifications
• 40 — request to read a notification when no notification is
pending
Performingconnectivitychecks
If you want to insert an RA440 Wireless Radio Modem into an existing
Adcon radio network, you should consider performing connectivity
checks before finishing installation of the device. Connectivity checks
are similar to the RTU connection checks. Before performing these
checks, you must have following items prepared:
• the A440 Serial number (printed on the type plate of the RA440)
• a serial communication cable (item number 200.720.540 from
your Adcon distributor)
The following instructions show you how to perform the connectivity
check:
1. After you check the connection to the A850 Telemetry Gateway
using the LED tool, disconnect the LED tool. A few seconds later,
connect your serial communication cable to the SOLAR CELL
connector.
2. Make a broadcast by entering the <A440_ID> B command, where
A440_ID is the serial number of your A440.
3. Wait at least 15 seconds.