User's Manual

CHAPTER3
Usingterminalcommands
44
type is used to represent the device type. The following types are
assigned currently:
— 0 for A730MD
— 1 for A720
— 2 for A730SD
— 3 for A720B
— 4 for A733
— 5 for A723
— 6 for A440
— 7 for A733 GSM
— 8 for A731
— 9 for A732
— 10 for A740
— 11 for A740 GSM
— 12 for A724
— 15 for A723_Series 4
— 16 for A724_Series 4
— 21 for A753GSM
— 24 fir RA440
slot and samples are the actual values programmed by means of
the SLOT command.
Note: The “slot” parameter has no relevance for the A440. The “samples”
parameter has no relevance for RA440 or the A440 (normally they
show 0).
po is the relative output power of the device.
Note: This parameter has no relevance for the RA440 (normally shows 0).
err_level is the error value; 0 means no error.
REMOTE Yes, GET only.
EXAMPLE # 441 info
441 info 0 31 01/01/1970 00:00:00 1.2 0 0 0 83 60 0 00:40 0
65 72 24 900 0 0 0
#
PMP
A
VAILABLE FOR RA440
DESCRIPTION Sets/returns the node’s Power Management Parameters (switches the
battery charge on/off).
PARAMETERS The lower (switch on) and the higher limit (switch off), both in volts x
10. Standard Values are 65 (for 6.5 volts) for switch on and 72 (for
7.2 volts) for switch off, for a standard 6.2 volt NiMH battery. From
these values, other thresholds are internally computed.
REMARKS GET/SET.