User's Manual

Table Of Contents
CHAPTER 3
Performing Advanced Functions
24
ID
4557 ID 4557 0
#
SLOT
 CAUTION Changing these parameters may adversely affect the
ability of the device to operate for extended periods under low sun
shine conditions.
DESCRIPTION Sets/returns the node’s sampling interval and rate.
PARAMETERS The interval (60 - 65535) and rate (0 - 255). The interval represents
the time (in seconds) elapsed between two slots stored in the inter-
nal memory, while the rate represents the numbers of samples
used to build the average that will be stored.
Note: The rate parameter is not relevant for the A725 RTU. The
sensors’ firmware is responsible for calculations of avaraged
values etc.
RETURNS The interval and rate.
REMARKS GET/SET. The default interval is 900 (15 minutes) and rate is 15 (15
samples per 15 minutes).
REMOTE Yes, SET only.
EXAMPLE SLOT 900 15
15535 SLOT 0
#
SLOT
15535 SLOT 900 15 0
#
PMP
DESCRIPTION Sets/returns the node’s Power Management Parameters (switches
the battery charge on/off).
PARAMETERS The lower (switch on) and the higher limit (switch off), both in volts
x 10. Standard Values are 65 (for 6.5 Volts) for switch on and 72 (for
7.2 Volts) for switch off (for a standard 6.2 Volt NiCd or NiMH bat-
tery). From these values, other thresholds are internally computed.
RETURNS The lower (switch on) and the higher limit (switch off), both in volts
x 10.