User's Manual

Table Of Contents
CHAPTER 3
Returned errors list
33
n is the desired valve voltage according to the following formula:
n = (UValve-5)*2

Note: The 1s ON time is always required for the MFS command. n
must be in the range of 1-20.
An example:
A valve voltage of 12 volt is required. The value for n therefore is
calculated as follows:
(12-5)*2 = 14
The port command is: PORT 208 1 14
Due to the use of MFS (Mono Flop Function), the programming
commands can be sent via the radio link, too. However, remote
programming is not recommended.
Returned errors list
Following are error messages you might get.
Command line interpreter
1 — nonexistent command
Table 4. addSWITCH Programming Commands
Step
addSWITCH
command
Setting up the programming mode PORT 159
Setting up UValve programming
mode
PORT 161
Setting up a monoflop function
(MFS) to program the desired
valve voltage
PORT 208 1 n
WAIT at least the time: n+1s, until
the MFS operation is completed!
-
Switch back to normal operating
mode
PORT 175