User's Manual

Table Of Contents
CHAPTER 3
Commands for controlling the valves
31
VER
DESCRIPTION Requests the firmware version of the device.
PARAMETERS None.
RETURNS The current version.
REMARKS GET only.
REMOTE No.
EXAMPLE VER
15535 VER 2.14.0 0
#
Commands for controlling the valves
Switching the valves
The valves can be controlled by the following commands:
Where n is the desired run-time in seconds (max. 65535, approx.
18h) and d is the startup delay in seconds (max. 65535, approx.
18h, the recommended minimum ist 1s).
 WARNING Do not use any other commands asdescribed here to
control the valves!
Reading status information
Using the PORT 0 command, the actual status can be read back.
For details on the returned value see the following table:
Table 2. addSWITCH Commands
Requested action addSWITCH A724 command
Open Valve 1 for n seconds PORT 208 d n
Open Valve 2 for n seconds PORT 209 d n
Close Valve 1 (before time
“n” is elapsed)
PORT 160
Close Valve 2 (before time
“n” is elapsed)
PORT 161