CHAPTER 3
Using terminal commands
23
RETURNS The node ID.
REMARKS GET/SET.
REMOTE Yes, SET only.
EXAMPLE ID 4557
15535 ID 0
#
ID
4557 ID 4557 0
#
SLOT
 CAUTION Changing these parameters may adversely affect the
ability of the device to operate for extended periods under low
sun shine conditions.
DESCRIPTION Sets/returns the node’s sampling interval and rate.
PARAMETERS The interval (60 - 65535) and rate (0 - 255). The interval represents
the time (in seconds) elapsed between two slots stored in the
internal memory, while the rate represents the numbers of samples
used to build the average that will be stored. The second parame-
ter is neglected by the A724 RTU.
RETURNS The interval and rate.
REMARKS GET/SET. The default interval is 900 (15 minutes) and rate is 15 (15
samples per 15 minutes).
REMOTE Yes, SET only.
EXAMPLE SLOT 900 15
15535 SLOT 0
#
SLOT
15535 SLOT 900 15 0
#
PMP
DESCRIPTION Sets/returns the node’s Power Management Parameters (switches
the battery charge on/off).