CHAPTER3
Usingterminalcommands
35
REMARKS The system stops, and exits the command only when a key is pressed.
This command returns no message.
REMOTE No.
EXAMPLE RX
41239 RX 0
#
SBAT
D
ESCRIPTION Sets/returns the operating voltage for the valves .
PARAMETERS The operating voltage of the valves in tenths of volt.
RETURNS The current setting.
REMARKS See also: Setting the valve voltage on page 42.
REMOTE No.
EXAMPLE SBAT
41239 SBAT 0 0 120 0
#
SLOT
CAUTION Changing these parameters may adversely affect the ability of the
device to operate for extended periods under low sunlight conditions.
DESCRIPTION Sets/returns the node’s sampling interval and rate.
PARAMETERS The interval (10 - 43200) and rate (0 - 255). The interval represents
the time (in seconds) elapsed between two slots stored in the internal
memory, while the rate represents the numbers of samples used to
build the average that will be stored. No average will be calculated for
the internal and the SDI-12 sensors. A third parameter can be used to
set the SLOT/SAMPLE settings for a specific connector.
Note: Not all combinations of SLOT/SAMPLE are accepted due to the time
alignment feature of A724 Series 4 RTU.
RETURNS The interval and rate.
REMARKS GET/SET. The default interval is 900 (15 minutes) and rate is 3 (5
samples per 15 minutes).
REMOTE Yes, SET only.
EXAMPLE SLOT 900 15
41239 SLOT 0
#