User's Manual

Table Of Contents
CHAPTER 3
Performing Advanced Functions
38
DESCRIPTION Substitution for the former IMME command. Please see A740 User
Guide for details.
PARAMETERS Please see A740 USer Guide.
RETURNS Please see A740 USer Guide.
REMARKS Only mode 2 is supported (there are no LCs or PCs for A7x3 Series
4). The ADC number is the same as the connector number, the
range parameter is ignored. If no connector number is given, data
for all connectors is returned.
Data format:
INTERNAL:
digibyte (SOLARCELL as bit 8)
battery voltage (0..255 = 0..20V)
temperature (0..255 = -68..332°C)
relative humidity (0..255 = 0..100%)
external voltage (0..255 = 0..20V)
IOA..IOD:
digibyte, with IO pin states *ONLY* for the given connector
(for IOD, the expansion port is included); bit numbers are the
same as with PORT RDP (PORT 0)
analog values for cabling 1..3 (0..65535 = 0..2,5V for standard
channels, 0..250mV for channels with low voltage amplifier
activated)
counter value
VALVES:
- digibyte, with IO pin states *ONLY* for the valves; bit numbers
are the same as with PORT RDP (PORT 0)
REMOTE Yes.
EXAMPLE XIMME 2 0
38193 XIMME
0 128 79 59 0 0
1 0 42240 13392 80 0
2 128 16400 32784 49072 24328