User's Manual

Table Of Contents
CHAPTER 3
Using terminal commands
27
RETURNS The current setting.
REMARKS GET/SET.
REMOTE Yes, via XCONF only.
EXAMPLE CALC
38193 CALC 3 7 0
#
CAlC 0x0FFF 3
38193 CALC 0
#
COMMAND DATA
DESCRIPTION Returns data stored for a certain device.
PARAMETER The ID of the device for which the data is requested and the date/
time (in the standard format) the data was stored. If missing, then it
refers to the data of the local device.
RETURNS A data block.
REMARKS GET only. If you don’t include the date/time parameter, the latest
data is returned. If you include the date/time parameter, the date
and time closest to, but later than, the given date/time is returned.
The DATA command can only be used with A73x and A72x non-
Series 4 RTUs. For A740, A73x Series4 and A72x Series 4 RTUs use
the XDATA command instead.
A complete description of the XDATA command can be found in
the A740 User Guide.
REMOTE Yes.
EXAMPLE DATA 5666 10/10/2008 12:34:56
38193 DATA b1 b2 b3 ... bn 0
#
The data block returned will typically contain a number of data
frames (telegrams). The structure of a block is as follows:
dd mm yyyy hh mm ss si ft d1 d2 ... dn dd mm yyyy
... dn cs