CHAPTER 3
Performing Advanced Functions
26
COMMAND PMP
DESCRIPTION Sets/returns the node’s Power Management Parameters (switches
on/off the battery charge).
PARAMETERS The lower (switch on) and the higher limit (switch off), both in volts
x 10. Standard Values are 65 (for 6.5 Volts) for switch on and 72 (for
7.2 Volts) for switch off.
RETURNS The lower (switch off) and the higher limit (switch on), both in volts
x 10.
REMARKS GET/SET.
REMOTE Yes, SET only.
EXAMPLE PMP 65 72
193 PMP 0
#
PMP
193 PMP 65 72 0
#
COMMAND CALC
DESCRIPTION Enables additional minimum (first parameter) and maximum (sec-
ond parameter) calculations for the analog values.
PARAMETERS Each parameter is a
bitmask
, the
channel
numbers have the same
meaning as with ANLG.
The format for the bitmask is:
bit 0: 1=enable calc. for ANLG channel 0
bit 1: 1=enable calc. for ANLG channel 1
bit 2: 1=enable calc. for ANLG channel 2
bit 3: 1=enable calc. for ANLG channel 3
and so on...