CHAPTER 3
Using terminal commands
25
RETURNS The interval and rate for all 7 connectors.
REMARKS The default
interval
is 900 (15 minutes) and
rate
is 3 (3 samples per
quarter of an hour).
REMOTE Yes, SET only.
EXAMPLE SLOT 900 3
38193 SLOT 0
#
SLOT SST
DESCRIPTION Sets/returns the sensor's settling time and measuring mode
PARAMETERS The settling time in seconds (0-255) and the measuring mode
(0=parallel, 1=sequential). If the connector is not specified, the
setting applies to all connectors except SDI.
If the settling time is set to zero, the sensor supply voltage for that
connector is turned off, if the settling time is equal or longer than
the sampling interval (SLOT rate divided by SLOT interval), the
sensor supply voltage is always turned on.
For the SDI connector, the SST is the sum of the measurement
times of the SDI sensors and specifies when the RTU begins to
query SDI sensors for measurement values.
RETURNS The interval and rate for all 7 connectors. See Table 2 for connec-
tor assignment.
REMARKS GET/SET.
REMOTE Yes, SET only.
EXAMPLE SST
38193 SST 2 0 2 0 2 0 0 0 0 0 0 0 0 0 0
#
SST 5 1 2
38193 SST 0
#
SST
38193 SST 2 0 2 0 5 1 0 0 0 0 0 0 0 0 0 0
#