L Manual

70
QUICKTRONIC
®
INTELLIGENT DIM (1…10 V) for compact fluo-
rescent lamps
Ordering designation for each type of lamp: QTi-T/E…DIM
Intelligent ECG with 1…10 V interface acc. to IEC 60929
OSRAM DULUX compact fluorescent lamps
®
T/E 18, 26, 32, 42 W
and OSRAM DULUX
®
T/E IN 26, 32, 42 (57) W (amalgam lamps)
unrestrictedly dimmable from 3 % to 100 %
Warm start of the lamp inside 0.6 seconds without switch-on
flash
Service life: 50,000 h at maximum thermal load (t
c
= 75 °C, max.
10 % failure)
Effective excess temperature protection of the dimming ECG
through intelligent power reduction at high t
c
temperatures
5-year system+ guarantee:
For every ECG that failed due to a material or production fault, a
replacement is available
CELMA energy classification EEI = A1
Maximum energy efficiency thanks to cut-off technology
EoL shutdown acc. to EN/IEC 61347-2-3 Section 17
For use in emergency lighting systems acc. to EN 50172 / DIN VDE
0108-100
Test mark: ENEC, VDE, EMC
EN 60929, EN 61347-2-3, EN 55015, EN 61000-3-2, EN 61547,
EN 61000-3-3
Ordering designation for each type of lamp: QTi-T/E…DIM
QUICKTRONIC
®
INTELLIGENT DIM (1…10 V) for T5/Ø 16 mm
fluorescent lamps
Ordering designation for each type of lamp: QTi … DIM
Intelligent ECG with 1…10 V interface acc. to IEC 60929
Operation of T5 fluorescent lamps of the same length in a luminaire
for the flexible adaptation of the light level
Unrestrictedly dimmable from 1 % to 100 %
Max. dimming speed for dynamic RGB color light applications of
5 ms, from 1 % to 100 % through optimized regulation of the fila-
ment preheating
Warm start of the lamp inside 0.5 seconds without switch-on
flash
Manual dimming operation (TouchDIM) without any control gear
with standard installation buttons, incl. memory function (double-
click) and soft start
Service life: 50,000 h at maximum thermal load (t
c
= 75 °C, max.
10 % failure)
5-year system+ guarantee
For every ECG that failed due to a material or production fault,
a replacement is available
CELMA energy classification EEI = A1
Maximum energy efficiency thanks to cut-off technology