L Manual

32
Note:
Only use switches without control lamp and with 230 V normally-
closed contact as the permanent current through the glow lamp
can lead to malfunctions
TouchDIM is not part of the DALI standard (IEC 62386), but rather
an additional OSRAM function
3.2.2 Operating parameters for TouchDIM
To operate the TouchDIM, AC voltages of 10…230 V (RMS) at
a frequency of 46…66 Hz can be used – there is no DC voltage
allowed.
3.2.3 Compensation of interferences
A control transformer which complies to the following figures and val-
ues must be used with a total line length from the switch to the ECG of
25 m to 100 m in order to prevent interference (e.g. through capacitive
induction):
Primary 230 V/Secondary 12 V, transformer rating required: 25 mW
per connected ECG (i.e. 150 mW with 6 ECGs 2 mA control current
per ECG)
DA
DA
~
~
L
N
PE
DALI ECG
Installation line
Button
12 V Transformer
Min. power: 25 mW x no. of ECGs
Figure 17: Control transformer for compensation close to the ECG
(e. g. in a luminaire)
DA
DA
~
~
L
N
PE
DALI ECG
Min. power: 25 mW x no. of ECGs
12 V Transformer
Button
Installation line
Figure 18: Control transformer close to the switch (e.g. in the subdis-
tributor or in a flush-mounted socket)