Datasheet

QUICKTRONIC PROFESSIONAL QTP5
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
03
Inrush current and max. number of ECG per circuit breaker
ECG Inrush Current Max. number of ECG per circuit breaker
Ip [A] TH [µs] B: 10A B: 16A C: 16 A
QTP5 1x14-35 24 230 17 28 47
QTP5 2x14-35 40 200 12 19 32
QTP5 3x14, 4x14 40 200 12 19 32
QTP5 1x24-39 24 230 17 28 47
QTP5 2x24-39 40 200 12 19 32
QTP5 1x49 24 230 17 28 47
QTP5 2x49 53 190 8 13 21
QTP5 1x54 40 200 12 19 32
QTP5 2x54 53 190 8 13 21
QTP5 1x80 40 200 12 19 32
Standards and approval marks
Dimensions & weight
Description
Safety: acc. to EN 61347-2-3 / IEC 61347-2-3
Radio interference: acc. EN 55015: 2006 + A1: 2007 + A2: 2009
Harmonic content: acc. to EN 61000-3-2 / IEC 61000-3-2
Immunity: acc. to EN 61547 / IEC 61547
A
pproval marks:
Description Length
[mm]
width [mm] height [mm] distance
mounting
holes [mm]
Weight [g]
QTP5 1x14-35 280 30 21 270 180
QTP5 2x14-35 360 30 21 350 255
QTP5 3x14, 4x14 280 40 21 270 240
QTP5 1x24-39 280 30 21 270 180
QTP5 2x24-39 360 30 21 350 255
QTP5 1x49 280 30 21 270 180
QTP5 2x49 360 30 21 350 255
QTP5 1x54 280 30 21 270 180
QTP5 2x54 360 30 21 350 255
QTP5 1x80 360 30 21 350 255