User Manual

QUICKTRONIC FIT T8
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded no guaranty will be provided.
TECHNICAL INFORMATION
06
Lamp/ECG System Combination
ECG
Lamp
HF lamp
wattage [W]
System
wattage [W]
Line current [A]
Luminous flux at
25°C [lm]
Luminous flux at
35°C [lm]
Power factor
[λ]
QT-FIT8 1x18
L18
16
19
0.09
1350
-
0.95
L16 ES
2
14.2
17.2
0.08
1100
-
0.90c
QT-FIT8 2x18
2x L18
2x16
36
0.16
2x 1300
-
0.98
2x L16 ES
2
2x14.2
32.4
0.14
2x 1100
-
0.97
QT-FIT8 3x18, 4x18
3x L18
3x16
54
0.25
3x 1350
-
0.97
3x L16 ES
2
3x14.2
47.1
0.21
3x 1100
-
0.98
4x L18
4x16
74
0.33
4x 1350
-
0.99
4x L16 ES
2
4x14.2
64
0.28
4x 1100
-
0.98
QT-FIT8 1x36
L36
32
36
0.16
3200
-
0.96
L32 ES
2
29
32
0.15
2500
-
0.93c
QT-FIT8 2x36
2x L36
2x32
71
0.32
2x 3200
-
0.98
2x L32 ES
2
2x29
64
0.30
2x 2500
-
0.97
QT-FIT8 3x36
3x L36
3x32
105
0.48
3x 3500
-
0.99
3x L32 ES
2
3x29
100
0.43
3x 2500
-
0.99
QTP8 1x58-70
L58
50
54
0.24
5000
-
0.96
L70
57
62
0.28
5900
-
0.96
L 51 ES
2
44.5
50
0.23
4200
-
0.96
QTP8 2x58-70
2x L58
2x50
109
0.48
2x 5000
-
0.98
2x L70
2x57
124
0.55
2x 5900
-
0.98
2x L 51 ES
2
2x44.5
96
0.43
2x4200
-
0.98
For more information on ECG refer to http://www.osram.com/ecg
For more information on System Guarantee refer to http://www.osram.com/guarantee
2
Additional Lamp-ballast combination without ENEC; ta = +10 °C to +50 °C