User Manual

QUICKTRONIC FIT T8
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded no guaranty will be provided.
TECHNICAL INFORMATION
03
Inrush current and max. number of ECG per circuit breaker
ECG
Inrush Current
Max. number of ECG per circuit breaker
Ip [A]
TH [µs]
B: 10A
C: 10A
B: 16A
C: 16 A
QT-FIT8 1x18
15
200
17
-
28
49
QT-FIT8 2x18
15
200
17
-
28
49
QT-FIT8 3x18, 4x18
15
200
8
-
13
22
QT-FIT8 1x36
15
200
17
-
28
49
QT-FIT8 2x36
15
200
8
-
13
22
QT-FIT8 3x36
15
200
8
13
13
22
QT-FIT8 1x58-70
15
200
17
28 28 49
QT-FIT8 2x58-70
15
200
8
- 13 22
Standards and approval marks
Dimensions & weight
Description
acc. to EN 61347-2-3 / IEC 61347-2-3
acc. EN 55015: 2006 + A1: 2007 + A2: 2009
acc. to EN 61000-3-2 / IEC 61000-3-2
acc. to EN 61547 / IEC 61547
Description
Length
[mm]
Width
[mm]
Height
[mm]
Distance
Mounting
Holes [mm]
Weight [g]
QT-FIT8 1x18
280
30
28
270
260
QT-FIT8 2x18
360
30
28
350
350
QT-FIT8 3x18, 4x18
280
40
28
270
370
QT-FIT8 1x36
280
30
28
270
270
QT-FIT8 2x36
360
30
28
350
350
QT-FIT8 3x36
280
40
28
270
390
QT-FIT8 1x58-70
280
30
28
270
280
QT-FIT8 2x58-70
360
30
28
350
350