User Manual
QUICKTRONIC FIT T8
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
03
Inrush current and max. number of ECG per circuit breaker
ECG
Inrush Current
Max. number of ECG per circuit breaker
Ip [A]
TH [µs]
B: 10A
C: 10A
B: 16A
C: 16 A
QT-FIT8 1x18
15
200
17
-
28
49
QT-FIT8 2x18
15
200
17
-
28
49
QT-FIT8 3x18, 4x18
15
200
8
-
13
22
QT-FIT8 1x36
15
200
17
-
28
49
QT-FIT8 2x36
15
200
8
-
13
22
QT-FIT8 3x36
15
200
8
13
13
22
QT-FIT8 1x58-70
15
200
17
28 28 49
QT-FIT8 2x58-70
15
200
8
- 13 22
Standards and approval marks
Dimensions & weight
Description
Safety:
acc. to EN 61347-2-3 / IEC 61347-2-3
Radio interference:
acc. EN 55015: 2006 + A1: 2007 + A2: 2009
Harmonic content:
acc. to EN 61000-3-2 / IEC 61000-3-2
Immunity:
acc. to EN 61547 / IEC 61547
Approval marks:
Description
Length
[mm]
Width
[mm]
Height
[mm]
Distance
Mounting
Holes [mm]
Weight [g]
QT-FIT8 1x18
280
30
28
270
260
QT-FIT8 2x18
360
30
28
350
350
QT-FIT8 3x18, 4x18
280
40
28
270
370
QT-FIT8 1x36
280
30
28
270
270
QT-FIT8 2x36
360
30
28
350
350
QT-FIT8 3x36
280
40
28
270
390
QT-FIT8 1x58-70
280
30
28
270
280
QT-FIT8 2x58-70
360
30
28
350
350