Installation Guide
40
QUICKTRONIC
®
T8 Instant Start
Universal Voltage Systems
www.sylvania.com
Lamp Striation Control
Normal Ballast Factor
Professional Series
QtP t8 isn
SYLVANIA QUICKTRONIC Professional
Series products are typically used in OEM
(original equipment manufacturers) stan-
dard fixtures and Trade/Distributor Basic
stocked products for replacement.
SYLVANIA QUICKTRONIC SYSTEM 32
UNV electronic T8 ballasts offer several
advantages:
1. Operate OCTRON T8 lamps with
maximum efficacy and high lumen
output
• 30-40% energy savings when
compared to F40T12 magnetically
ballasted systems (see table below)
2. Parallel Circuitry: keeps remaining
lamps lit if one or more go out
3. Small Can Enclosure for:
• low profile fixture design
• transportation, inventory and
ergonomic benefits
4. Lamp Striation Control (LSC):
T8 energy saving lamps should be
operated above 60°F, but under certain
conditions the lamps may striate. LSC
circuitry may minimize or eliminate this
condition; however there are limited
applications where LSC circuitry may
not entirely mitigate lamp striations
These ballasts are also RoHS compliant
and feature lead-free solder and
manufacturing process.
Setting the standard for quality,
QUICKTRONIC T8 Instant Start 32
UNV-ISN systems are covered by the
QUICK 60+
®
warranty, the first and
most comprehensive lamp & ballast
system warranty in the industry.
Lamp / Ballast Guide
System Information
32W T8 - OCTRON
®
lamps
1-lamp QTP1x32T8/UNV ISN-SC
2-lamp QTP2x32T8/UNV ISN-SC
3-lamp QTP3x32T8/UNV ISN-SC
4-lamp QTP4x32T8/UNV ISN-SC
Also operates:
FBO32, FBO31, FO25, FBO24, FO17,
FBO16, FO30/SS (30W), FBO30/SS
(30W), FBO29/SS (29W), FO28/SS (28W)
& FO25/SS (25W)
FO40T8 operation:
1 lamp on 2L ballast, 2 lamps on 3L
ballast, 3 lamps on 4L ballast
SYLVANIA QUICKTRONIC SYSTEM 32 (QTP)
UNV system advantages:
• Operate from 120V through 277V
• Eliminates “wrong voltage” errors
• Reduces inventory by 50%
• Utilizes Instant Start operation for
• Highest System Efcacy
• Low temperature starting capability
• Very low harmonic distortion (<10%)THD
• Operate at >42 kHz to reduce potential
interference with infrared control systems
• Customers should always consider
upgrading to our High Efficiency
Systems to maximize energy savings
Relative
Input Initial System Mean Mean
System Power System Efficacy System Light Energy
Type (W) Lumens LPW Lumens Output Savings
F40T12 - Std. Magnetic Ballast 96 5795 60 4925 Baseline Baseline
E.S. Magnetic Ballast 86 5795 67 4925 Baseline 10%
F34T12 - Std. Magnetic Ballast 82 4665 58 3965 81% 15%
E.S. Magnetic Ballast 72 4665 66 3965 81% 25%
FO32/XP - QTP2x32T8/UNV-ISN-SC 59 5280 89 4965 101% 39%
FO28/SS - QTP2x32T8/UNV-ISN-SC 52 4795 92 4510 92% 46%
• Universal voltage (120-277V)
• Small can enclosure size
• Lamp Striation Control (LSC)
• 0.88 ballast factor
• 30-40% energy savings
• Min. Starting Temp:
• -20°F (-29°C) for T8 lamps
• 60°F (16°C) for Energy Saving
T8 lamps
• 0°F (-18°C) for FO40T8 lamps
• <10% THD
• Virtually eliminates lamp icker
• RoHS compliant
• Lead-free solder and manufacturing
process
Key System Features
SYLVANIA QUICKTRONIC
32 UNV ballasts
are ideally suited for:
• Commercial
• Retail
• Hospitality
• Institutional
• New Construction
• Retrot
Application Information
2-FO28/SUPERSAVER
QTP 2x32T8/UNV ISN
92%
54%
46%
Energy
Savings
2-FO32/XP/ECO
QTP 2x32T8/UNV ISN
101%
61%
39%
Energy
Savings
2-F40T12
Std. Magnetic Ballast
100% 100%
40%
50%
60%
70%
80%
90%
100%
110%
% Relative Light Output
(Mean Lumens)
% System Wattage
(Power)