Installation Manual
Table Of Contents
Appendix A Installation In-
Dispenser
A.1. General
This section describes how to install the nWGT unit inside of a dispenser.
MANUFACTURER AND LIMITATION OF LIABILITY DISCLAIMER:
Users (all parties involved in designing, preparing, or implementing the nWGT installation
process, and excludes Orpak and any party representing Orpak) are responsible for
following all guidelines and regulations regarding the installation conditions, including
those which apply to other products installed in the gas station (whether Orpak’s or not).
Installation of the nWGT in/on a dispenser is prohibited unless the dispenser’s
manufacturer written permission to do so was received in advance.
In no event shall Orpak be liable for any damage caused to the pump, dispenser, or any
internal components due to improper compliance with this manual or the manual of any
related products. Any direct, indirect, or incidental damages are the sole responsibility of
the user.
CAUTION:Installation inside of a dispenser is not recommended by Orpak, and must be
performed in compliance with all standards, precautions, and guidelines detailed
Preliminary Considerations.
A.2. In-Dispenser Installation Guidelines
For in-dispenser nWGT installations, adhere to the following guidelines:
When installing the nWGT in a dispenser, follow all relevant guidelines from the dispenser
manufacturer. Guidelines may vary according to dispenser model and manufacturer.
Install the nWGT in a vacant area within the dispenser head; make sure it is at least 25x25cm
In cases where the nWGT functions as the Master nWGT, it should be connected to the FCC
controller using shielded S-CAT5E LAN or an RS485 cable. Install the master nWGT as close as
possible to the FCC controller
Verify that the dispenser head enclosure is not made completely of metal as it will block the RF
transmissions
For ease of maintenance, it is recommended not to install the nWGT higher than two meters from
the ground. However, the higher will be the unit; the better will be the RF coverage
The installation procedures must meet all safety measures according to local state regulations
Locate a 110-240 VAC power source for the nWGT's power supply
Prior to installation procedures turn off all dispenser head (CPU) power sources
UL listed nWGT boxes are provided with provisions for conduit connection allowing using UL
approved tubes for power lines. The conduits grips/fittings are not sufficient for this purpose
For non-UL nWGT, couplers are provided for the power and data holes
26 nWGT Installation Manual