User Manual

optris CS E2012-10-B
20
On the model CSTCLT15 you can choose between a mV output (0-5 or 0-10 V; scalable via software) and a
thermocouple output type K.
The factory default setting is thermocouple output. Factory default settings
This output supplies a voltage according to the t/c characteristic curve type K.
If you want to extend this output you have to use a suitable thermocouple extension cable (NiCr-Ni).
Digital communication
For a digital communication the optional USB programming kit is
required. Please connect each wire of the USB adapter cable with the
same coloured wire of the sensor cable by using the terminal block.
Press with a screw driver as shown in the picture to loose a contact.
IMPORTANT: The shield [black] on the CS is not connected to GND [brown].
In any case it is necessary to connect the shield to ground or GND (whichever works best)!