Owner's manual

27
9. Warranty
Warranty on this product is valid against defects in material and workmanship
for a period of 24 months from its original date of purchase.
10. Technical Specifications
10.1 Power Range 1000-3000 VA (100/110/120V)
GENERAL
Rated power 1000 VA, 1500VA, 2000 VA, 3000 VA at p.f 0.7
Technology On-line, double conversion topology with automatic bypass
INPUT
Phase: Single phase with ground
Bypass Voltage 96--138 VAC (user selectable)
Input Voltage range: 60/70/80VAC-144 VAC
Frequency: 50/60 Hz. Auto selection
Frequency window from mains 45-65 Hz
Synchronization window ± 3Hz.
Input current 1000 VA 8.2A, 1500 VA 12.3A, 2000 VA 16.5A, 3000 VA 24.7A
Input Power factor: 0.97
OUTPUT
Output Voltage: 100/110/115/120/127 VAC, selectable from LCD panel
Voltage regulation: ± 2%
Voltage distortion: < 5% THD at full non-linear load, < 3% THD at full linear load
Frequency regulation ± 0.25 Hz (battery or free running mode)
* 60V at 40% load, 70V at 70%, 80V at 100%.
ENVIRONMENTAL
Ambient temperature: +0 °C to +40 °C
Recommended temperature: +15 °C to +25 °C
Storage temperature: -15 °C to +50 °C
Cooling: Forced air-cooling
Humidity: 0-95%, non-condensing
Audible noise: < 40 db normal and battery mode
10.2 Power Range 1000-3000 VA (220/230/240V)
GENERAL
Rated power 1000 VA, 1500 VA, 2000 VA, 3000 VA at p.f. 0.7
Technology On-line, double conversion topology with automatic bypass
INPUT
Phase Single phase with ground
Bypass Voltage: 184-265 VAC (user selectable)
28
Input Voltage range: 120/140/160 VAC-276 VAC
Frequency: 50/60 Hz. Auto selection
Frequency window from mains 45-65 Hz
Synchronization window ± 3Hz.
Input current 1000 VA 4A, 1500 VA 6A, 2000 VA 7.7A, 3000 VA 12A
Input Power factor: 0.97
OUTPUT
Output Voltage: 208/220/230/240 VAC, selectable from LCD panel
Voltage regulation: ± 2%
Voltage distortion: < 5% THD at full non-linear load, < 3% THD at full linear load
Frequency regulation ± 0.25 Hz (battery or free running mode)
* 120V at 40% load, 140V at 70%, 160V at 100%.
Dynamic response: ± 9 % max from 100% to 20 % or from 20% to 100 % linear load
Overload capacity: 100-125% 1 min, 125-150% 10 sec
Efficiency: greater than 86%
ENVIRONMENTAL
Ambient temperature: +0 °C to +40 °C
Recommended temperature: +15 °C to +25 °C
Storage temperature: -15 °C to +50 °C
Cooling: Forced air-cooling
Humidity: 0-95%, non-condensing
Audible noise: < 40 db normal and battery mode
10.3 Power Range 1000-3000 VA (100/110/120V 19” Rack-mount
model)
GENERAL
Rated power 1000 VA, 1500 VA, 2000 VA, 3000 VA at p.f. 0.7
Technology On-line, double conversion topology with automatic bypass
INPUT
Phase: Single phase with ground
Bypass Voltage 96--138 VAC (user selectable)
Input Voltage range: 60/70/80VAC-144 VAC
Frequency: 50/60 Hz. Auto selection
Frequency window from mains 45-65 Hz
Synchronization window ± 3Hz.
Input current 1000 VA 8.2A, 1500 VA 12.3A, 2000 VA 16.5A, 3000 VA 24.7A
Input Power factor: 0.97
OUTPUT
Output Voltage: 100/110/115/120/127 VAC, selectable from LCD panel
Voltage regulation: ± 2%
Voltage distortion: < 5% THD at full non-linear load, < 3% THD at full linear load