Manual

4-5
(c) Close the rectifier breaker - The rectifier will be automatically started if the
power source connected is correct. The DC voltage will slowly
rise up (15 30sec.) until the designated voltage is reached, and
will keep the value anyhow. Now, the DC is already ready for the
inverter.
(d) Close the battery breaker - A fuse holder is employed in the battery to the
DC bus for
safety
purpose.
Now the batteries will take-over to
supply the DC bus if rectifier mains fail.
(e) Push inverter on switch To on the inverter, the inverter on switch and the
control switch must be pressed simultaneously. The inverter will
start working and inverter output will be established in 4 sec. The
load will be automatically transferred to the inverter 3 sec. later.
Now the UPS comes again into normal operation now.