3.3. Cable Selection
The following tables list all the information between KVA of the UPS and the size
and rating of the cables. Inadequate cable size or over sized breaker will incur risk
of fire or damage of insulation. Therefore, please look up the following tables to
determine the input circuit breaker rating and the size of cable for input, output and
battery connections. These data are for reference; final decision should be made in
accordance with the local electrical regulations.
BREAKER RATING FOR INPUT
KVA INPUT Imax(A) NFB(A)
20
230/400V 3Φ
50
50
30
230/400V 3Φ
73
75
40
230/400V 3Φ
98
100
50
230/400V 3Φ
122
125
60
230/400V 3Φ
147
150
80
230/400V 3Φ
172
175
100 230/400V 3Φ
215
225
120
230/400V 3Φ
258
300
160
230/400V 3Φ
344
350
240
230/400V 3Φ
520
500
320
230/400V 3Φ
692
700
CABLE SIZE FOR INPUT
KVA INPUT In(A) R/S/T(mm
2
) N(mm
2
)
20
230/400V 3Φ
36
8
14
30
230/400V 3Φ
54
14
22
40
230/400V 3Φ
72
22
30
50
230/400V 3Φ
90
30
38
60
230/400V 3Φ
108
38
50