Manual

2-11
KVA
200 240 300 320
INVERTER
DC INPUT RANGE 285 – 415VDC
WAVE FORM SINUSOID
OUTPUT VOLTAGE
380 / 400 / 415 V 3 PHASE WITH
NEUTRAL
OUTPUT POWER FACTOR 0.8
VOLTAGE REGULATION
0-100% LOAD
+ / - 1 %
FREQUENCY LOCK RANGE 45 – 55 Hz / 55 – 65 Hz
OUTPUT FREQUENCY
(FREE RUNNING)
50 / 60 Hz + / - 0.1 Hz
PHASE DIFFERENCE WITH
RESERVE INPUT
120
°
+ / -
0.5
°
THD (LINEAR LOAD) < 5 %
OVERLOAD
- <110% CONTINUOUS
- 110 – 125% 15
min
- 125 – 150% 10
min
- > 150% 60 sec
EFFICIENCY(100% LOAD) 95% 95% 95% 95%
MAXIMUM OUTPUT
PEAK CURRENT(A)
800
1000
1250
1300
STATIC SWITCH
VOLTAGE RANGE 173 – 277 VAC (LINE TO NEUTRAL)
FREQUENCY RANGE 45 – 55 Hz / 55 – 65 Hz
EFFICIENCY 99.5%
TRANSFER TIME:
- MAINS -> INVERTER
0
ms
- INVERTER -> MAINS 0
ms
OVERLOAD
- 100% 30 sec
-
300%
1 sec
ISOLATION WITH OUTPUT
YES