Manual

2-6
KVA
80
100 120 160
OVERALL
CHARACTERISTICS
OVERALL EFFICIENCY 92.5%
92.5%
93% 93%
OPERATING ENVIRONMENT:
- TEMPERATURE
0 - 40 ( 32 -
104
)
- HUMIDITY 0% - 90% ( NONCONDENSING )
-
ALTITUDE <1500 M ABOVE SEA LEVEL
MAXIMUM HEAT
DISSIPATION(KW)
4.6
5.4
6.5
8.7
WEIGHT(Kg) 820 950 1180 1450
DIMENSION:
- HEIGHT(mm)
1600
- WIDTH(mm)
1100
- DEPTH(mm)
800
-
AUDIBLE NOISE < 65 dBA (AT 1 m)
STANDARDS:
- EN50091-1,-2
YES
- FCC CLASS A
YES
PROTECTIONS:
- SHORT CIRCUIT RECTIFIER, RESERVE, BYPASS NFB
- LIGHTNING
MOV
- EMC FILTER INPUT & OUTPUT
- GALVANIC ISOLATION BETWEEN INPUT & OUTPUT
DATA DISPLAY BY LCD
YES
INDICATIONS & ALARMS:
- LED,LCD,BUZZER
YES
DRY CONTACT
YES
BATTERY START
YES
All specifications mentioned above are subject to change without prior notice.