NT31 NT31C Programmable Terminals Setup Manual

5-2SectionConnecting to the Host’s RS-422A/485 Port
118
C500-LK203
3G2A6-LK202-EV1
1
14
13 25
NT31/NT31C side
Shielding wire
(25-pin type)
Abbreviation
FG
SD
RD
RS
CS
SG
TRM
RDB (+)
SDB (+)
SDA ()
RDA ()
RSB (+)
RSA ()
Pin number
Connector
hood
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
23
24
25
RS-232C/
422A/485
connector
6
5
9
1
PC side
RS-422A
connector
Pin number
Connector
hood
1
2
3
4
5
6
7
8
9
Abbreviation
FG
RDB
SDB
RDA
FG
SDA
(9-pin type)
In order to avoid an FG ground loop, do not connect the functional ground of the
NT31/NT31C to the shielding of the RS-422A cable.
Wiring When Connecting CPM1, CPM2A, CPM2C, or SRM1
Applicable units:
CPM1-10CDR- CPM1-20CDR-
CPM1A-10CD- CPM1A-20CD-
CPM1A-30CD- CPM1A-40CD-
CPM2A-30CD- CPM2A-40CD-
CPM2A-60CD-
CPM2C-10- CPM2C-20-
SRM1-C02-V2
Connect to the PC through a CPM1-CIF11 RS-422A Adapter.
1
14
13 25
NT31/NT31C side
Shielding wire
(25-pin type)
Abbreviation
FG
SD
RD
RS
CS
SG
TRM
RDB (+)
SDB (+)
SDA ()
RDA ()
RSB (+)
RSA ()
Pin number
Connector
hood
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
23
24
25
RS-232C/
422A/485
connector
PC side
RS-422A
terminal
block
Abbreviation
FG
SG
SDB (+)
SDA ()
RDB (+)
RDA ()
(9-pin type)
FG
SG
SDB
SDA
RDB
RDA
In order to avoid an FG ground loop, do not connect the functional ground of the
NT31/NT31C to the shielding of the RS-422A cable.