Datasheet

G2R
G2R
3
Specifications
Coil Ratings
Rated voltage
12 VAC 24 VAC 100/
(110) VAC
120 VAC 200/
(220) VAC
220 VAC 230 VAC 240 VAC
Rated current* 50 Hz
93 mA 46.5 mA 11 mA 9.3 mA 5.5
(4.0) mA
5.1 mA 4.7 (3.7)
mA
4.7 mA
60 Hz
75 mA 37.5 mA 9/
(10.6) mA
7.5 mA 4.5
(5.3) mA
4.1 mA 3.8 (3.1)
mA
3.8 mA
Coil resistance*
65
!
260
!
4,600
!
6,500
!
20,200
(25,000)
!
25,000
!
26,850
(30,000)
!
30,000
!
Coil inductance Armature OFF
0.19 0.81 13.34 21 51.3 57.5 62 65.5
(H) (ref. value) Armature ON
0.39 1.55 26.84 42 102 117 124 131
Must operate voltage
80% max. of rated voltage
Must release voltage
30% max. of rated voltage
Max. voltage
110% of rated voltage
Power consum ption
Approx. 0.9 VA at 60 Hz (approx. 0.7 VA at 60 Hz)
Note:
1. Rated voltage of bifurcated crossbar contact type: 100/(110) VAC, 200/(220) VAC, 230 VAC (Approx. 0.7 VA at 60 Hz)
2. Depending on the type of Relay, Some Relays do not have coil specifications. Contact your OMRON representative for more de-
tails.
Rated voltage
5VDC 6VDC 12 VDC 24 VDC 48 VDC 100 VDC
Rated current* (50/60 Hz)
106 mA 88.2 mA 43.6 mA 21.8 mA 11.5 mA 5.3 mA
Coil resistance*
47
!
68
!
275
!
1,100
!
4,170
!
18,860
!
Coil inductance Armature OFF
0.20 0.28 1.15 4.27 13.86 67.2
(H) (ref. value) Armature ON
0.39 0.55 2.29 8.55 27.71 93.2
Must operate voltage
70% min. of rated voltage
Must release voltage
15% min. of rated voltage
Max. voltage
110% of rated voltage
Power consum ption
Approx. 0.53 W
Note:
Rated voltage of bifurcated crossbar contact type: 12 VDC, 24 VDC
High-sensitivity Relays
Rated voltage
5VDC 6VDC 12 VDC 24 VDC 48 VDC
Rated current (50/60 Hz)
71.4 mA 60 mA 30 mA 15 mA 7.5 mA
Coil resistance
70
!
100
!
400
!
1,600
!
6,400
!
Coil inductance Armature OFF
0.37 0.53 2.14 7.80 31.20
(H) (ref. value) Armature ON
0.75 1.07 4.27 15.60 62.40
Must operate voltage
70% max. of rated voltage
Must release voltage
15% max. of rated voltage
Max. voltage
110% of rated voltage
Power consum ption
Approx. 0.36 W
*Note:
1. The rated current and coil resistance are measured at a coil temperature of 23
"
C with atolerance of
+15%
/
-20%
(AC rated current) or
#
10% (DC coil resistance).
2. LEDs are used for the built-in operation indicator . For models equipped with these indications, the VAC rated current must be in-
creased by approximately 1 mA; the VDC rated current, by approximately 4 mA.
3. Operating characteristics are measured at a coil temperature of 23
"
C.