User Guide
Klinkmann Automation Omron Ethernet DAServer  59 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3    17014m13 
operation manual) 
  04  Node number setting 
error. 
Make sure the node 
number is within 
specified range and that 
there are no duplicate 
node numbers. 
DASProtFail 
04: Not 
executable 
01  An undefined 
command has been 
used, or short frame (4 
bytes) is being used for 
FINS header frame. 
Check the command 
code and be sure code 
is supported by Unit to 
which command is 
sent.(*) 
DASProtFail 
05: Routing 
error 
01  Destination node 
number is not set in the 
routing tables. 
Set the remote PLC in 
the routing tables. 
DASProtFail 
  02  Routing tables aren't 
registered. 
Set the the routing 
tables at the relay nodes 
and remote node. 
DASProtFail 
  03  Routing table error.  Set the the routing 
tables correctly. 
DASProtFail 
  04  The maximum number 
of relay nodes (2) was 
exceeded in the 
command. 
Redesign the network to 
reduce number of relay 
nodes. 
DASProtFail 
10: 
Command 
format error 
01  The command is longer 
than the max. 
permissible length. 
Check the command 
format and set it 
correctly.(*) 
DASProtFail 
  02  The command is 
shorter than the min. 
permissible length. 
Check the command 
format and set it 
correctly.(*) 
DASProtFail 
  03  The designated 
number of data items 
differs from the actual 
number. 
Check the number of 
items and data and 
make sure that they 
agree.(*) 
DASProtFail 
  05  An incorrect header 
has been used. (Data 
for another node was 
received. Attempt was 
made to send response 
to broadcast address) 
Check the header 
parameters in the 
command and be sure 
the correct command 
format is used.(*) 
DASProtFail 
11: 
Parameter 
error 
00  The parameter in the 
command data were 
incorrect or the 
Check the parameters 
and be sure the socket 
number is between 1 
DASProtFail 