Klinkmann Automation Omron Ethernet DAServer  46 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3    17014m13 
practical application, OPC clients 
should reference $SYS$Status 
at any hierarchy levels other 
than the root. 
$SYS$ErrorCode  Longint/ 
Read 
Detailed error code of the 
communications state to the 
device. The device group (OPC 
access path/topic) does not 
affect the value. 
>= 0: Good 
status (0 is the 
default state – 
connected. 
>0: is some 
device state like: 
connecting, 
initializing, etc. 
<0: Error status 
(value indicates 
the error). 
$SYS$ErrorText  String/ 
Read 
Detailed error string of the 
communications state of the 
device. The device group (OPC 
access path/topic) does not 
affect the value. 
Descriptive text 
for the 
communications 
state 
corresponding to 
the error code.  
$SYS$StoreSettings 
Integer/ 
ReadWrite 
Used to make the temporary 
update interval changes via the 
$SYS$UpdateInterval item 
permanent. If the client pokes a 
value of 1 into this system item, 
the currently set update interval 
is written to the server’s 
configuration file. The value of 
this system item clears to 0 after 
being set, if the configuration file 
write is successful. 
If the write fails, then the value is 
set to -1. 
If the update interval has been 
changed via the 
$SYS$UpdateInterval item and 
this item is not poked to 1, the 
DAServer uses the original 
update interval for that topic the 
next time it is started. 
Reading the item always 
provides 0. 
Read/Write values are persisted 
only if the user sets this system 
item. The values other than this 
persist only for the life of the 
DAServer. 
RANGE: -1, 0, 1 
-1: Error 
occurred during 
saving the 
configuration file. 
0: Read value 
always if status is 
OK. 
1: Persist 
settings (cleared 
immediately). 