Server User Manual
Klinkmann Automation Omron Ethernet DAServer  56 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4    17014m14 
Error Messages and Codes 
Generic DAServer error messages and Omron Ethernet-DAServer-specific messages are 
supported. Use the Log Flag data to customize the messages logged to the Log Viewer. 
See the Log Viewer online documentation for more information about using log flags. 
To troubleshoot DAServer problems, use the following error messages together with the 
DAServer Manager Diagnostics root data. 
DAServer Error Messages 
The following table lists all the generic-DAServer and Omron Ethernet-DAServer-specific 
error messages that are logged to the Log Viewer. 
Error Message  Explanation  Probable Cause  Solution  Log Flag 
OmronEthAdapter 
<SockName>: Invalid 
local Host Name (IP 
Address) 
<WrongName>. 
Further operate with 
Host name: 0.0.0.0 !!! 
Windows 
Sockets API 
functions do 
not accept Host 
Name (IP 
Address) value.
Configured invalid 
Host Name (IP 
Addr.) parameter 
for SOCKET 
<SockName >. 
Enter correct 
Host Name or 
IP Address. 
Error 
<Socket_ 
ControllerName>: 
Invalid PLC's 
IPAddress 
<WrongIPAddress> 
Windows 
Sockets API 
functions do 
not accept  
Controller IP 
Address value. 
Configured invalid 
Controller IP 
Address 
<WrongIPAddress
> 
Enter correct 
Controller IP 
Address. 
Error 
Socket <SockName> 
::OnMessageToSend
, Creating Eth. 
Socket get Error 
<Error number>: 
<Error description> 
Failed creating 
Ethernet 
Socket by 
Windows 
Sockets dlls 
For reason - see 
Error description in 
the message. 
Most possible 
cause - Ethernet 
Port already 
occupied by other 
OMRON Ethernet 
DAServer socket or 
other application. 
Solve 
problems 
mentioned in 
Error 
description. 
Avoid 
concurrently 
communicatio
n through 
Sockets with 
equal Port 
numbers. 
DASProtFail 
 <Socket_ 
ControllerName>: 
Can not create 
Watchdog Message. 
Do not process 
Watchdog. 
Failed creation 
of Watchdog 
message. 
Watchdog 
message is not 
processed until 
solving the 
problems. 
Invalid Watchdog 
Address or Invalid 
Watchdog value. 
Watchdog Address 
area could be non-
supported by 
current DAServer 
version. 
Enter correct 
Watchdog 
Address (right 
Item name 
representing 
2-bytes long 
Word 
memory area 
without 
suffix). Enter 
Watchdog. 
Error 