Memory Area  Prefix
Tag 
Type 
Range  Value 
Range 
Format 
Suffix 
IR & SR areas 
(Bit status)(***) 
IR 
Discrete 
IR0:00...IR255:15 
or 0.00...255.15 
0, 1   
IR & SR areas 
(Word contents) (***) 
 IR 
Integer  IR0...IR255 
or 0...255 
(*)  u s b f g l 
m d e c 
Latching Relay area 
 (Bit status) 
LR 
Discrete
LR0:00... LR15:15 
0, 1   
Latching Relay area 
(Word contents) 
LR 
Integer  LR0... LR15  (*)  u s b f g l 
m d e c 
Holding Relay area 
 (Bit status) 
HR 
Discrete
HR0:00... HR19:15 
0, 1   
Holding Relay area 
(Word contents) 
HR 
Integer  HR0... HR19  (*)  u s b f g l 
m d e c 
Auxiliary Relay area 
 (Bit status) 
AR 
Discrete
AR0:00... AR23:15 
0, 1   
Auxiliary Relay area 
(Word contents) 
AR 
Integer  AR0... AR23  (*)  u s b f g l 
m d e c 
Completion flags for 
Timers/Counters(**) 
TC 
Discrete
TC0... TC255  0, 1   
Present Values for 
Timers/Counters 
PV 
Integer  PV0... PV255  (*)  u s b f g l 
m d e c 
Data Memory area 
(Bit status) (****) 
DM 
Discrete
DM0:0...DM6655:15 
0, 1   
Data Memory area 
(Word contents) (****)
DM 
Integer  DM0... 
DM6655 
(*)  u s b f g l 
m d e c 
Item/point names, corresponding to IR and SR areas, may be without prefix. 
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U" 
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with 
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is 
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default 
value range for Integer Tag Type is unsigned integer. 
(**) Read only 
(***) Addresses 50 to 199 in IR & SR area in CPM2A/CPM2C PLCs and 20 to 199 in IR & 
SR area in CPM1/CPM1A/SRM1(-V2) PLCs are read only. 
(****) Addresses DM1024 to DM6143 in CPM1/CPM1A PCs and DM2048 to DM6143 in 
CPM2A/CPM2C/SRM1(-V2) PCs are read only. 
The following examples show the correct format for item names for C/CPM2x PLCs: 
IR2:01 -  CIO area (Bit status), word address 2, bit number 1. 
 211  - CIO area (Word contents), word address 211. 
 LR62.10 -  Latching Relay area (Bit status), word address 62, bit number 10. 
 DM21 -  Data Memory area (Word contents), word address 21. 