Server User Manual
Klinkmann Automation Omron Ethernet DAServer  40 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4    17014m14 
C200HX/C200HG/C200HE PLCs 
The following table lists the supported item names for the C200HX, C200HG and 
C200HE PLCs. 
Memory Area  Prefix
Tag 
Type 
Address Range  Value 
Range 
Suffix 
Internal Relay Area 1, 2 
Special Relay Area 1, 2 
(Bit status) 
 IR 
Discrete 
IR0:00...IR511:15 
or 
0.00...511.15 
0, 1   
Internal Relay Area 1, 2 
Special Relay Area 1, 2 
(Word contents) 
IR 
Integer  IR0... IR511 
or 
0…511 
(*)  u s b f g l 
m d e c 
Link Relay Area 
 (Bit status) 
LR 
Discrete
LR0:00...LR63:15 
0, 1   
Link Relay Area 
(Word contents) 
LR 
Integer  LR0... LR63  (*)   
Holding Relay Area 
 (Bit status) 
HR 
Discrete
HR0:00... HR99:15
0, 1   
Holding Relay Area 
(Word contents) 
HR 
Integer  HR0... HR99  (*)  u s b f g l 
m d e c 
Auxiliary Relay Area 
 (Bit status) 
AR 
Discrete
AR0:00... AR27:15
0, 1   
Auxiliary Relay Area 
(Word contents) 
AR 
Integer  AR0... AR27  (*)  u s b f g l 
m d e c 
Timer/Counter Area 
Completion Flag(****) 
TC 
Discrete
TC0... TC511  0, 1   
Timer/Counter Area 
(PV) 
PV 
Integer  PV0... PV511  (*)  u s b f g l 
m d e c 
Data Memory Area 
(Bit status)(**) 
DM 
Discrete
DM0:00... 
DM9999:15 
0, 1   
Data Memory Area 
(Word contents)(**) 
DM 
Integer  DM0... 
DM9999 
(*)  u s b f g l 
m d e c 
Extended Data Memory 
Area (Bit status)(***) 
EM 
Discrete
EM0:00... 
EM6143:15 
0, 1   
Extended Data Memory 
Area Word contents(***) 
EM 
Integer  EM0... EM6143  (*)  u s b f g l 
m d e c 
Item/point names, corresponding to Internal Relay/Special Relay Area may be without 
prefix. 
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U" 
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with 
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is 
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default 
value range for Integer Tag Type is unsigned integer. 
(**) Memory area range DM7000…DM9999 is supported only if Expansion DM Area is 
allocated on the PLC. 