Server User Manual
Klinkmann Automation Omron Ethernet DAServer  37 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4    17014m14 
High-order Byte  Only the high-order byte (MSB - most significant 8-bits) of each 
word is used for read. To use this format, append the suffix 'D' 
to the item name. 
Both Bytes  Both bytes of each word are used for read/write. To use this 
format, append the suffix 'C' to the item name. 
Note: All bytes in the specified memory range will be used. If the string is shorter 
than the range of memory specified, it will be padded with '\0'. If the string is longer 
than the range of memory specified, the string will be truncated. 
For example, assume the following memory contents (numeric values shown in 
hex): 
MSB
LSB
DM10
41  42  "AB"
DM11
43  44  "CD"
DM12
45  46  "EF"
Read: 
DM10 – DM12C
returns ABCDEF 
DM10 – DM11D
returns AC 
DM10 – DM12E
returns BDF 
Write: 
DM10 - DM12C  after written with "ABCD" 
MSB
LSB
DM10
54  65  "AB"
DM11
73  74  "CD"
DM12
0  0  " " 
DM10 - DM12E  after written with "ABCDE" 
MSB
LSB
DM10
0  41  "A" 
DM11
0  42  "B" 
DM12
0  43  "C" 
Imortant Note! 
Do not operate with item names, which have addresses outside really existing PLC 
data and memory area! It will lead to communication failures, because the DAServer 
recognizes item name error only if item name goes out of range represented in the item 
names table. Usually the information like following will be logged to logger if some item 
with address in inaccessible memory area is used (MRC:11 and SRC:03 informs about 
"Parameter error: the first address is in an inaccessible area") 
<Socket.Controller>: FINS command 0101 failed (resp. error code 1103). Parameter 
error: the first address is in inaccessible area. 