Controller Link Units Operation Manual
198
Using the Message Service Section 6-3
CVM1 and CV-series PLCs
Note When using the sample program, make sure that the bits and words used in
the sample program are not the same as those in the user program or Special
I/O Units.
 (011)
I0000
00
A502
07
1200
02H
1200
01H
1210
00H
 (030)
 (030)
 (030)
 (030)
 (030)
 (040)
 (192)
 (013)
1200
00
A502
15
 (011)
 KEEP 120002H
I0000
01
A502
07
1200
00H
1200
03H
 (030)
1200
02H
(030) 
 (030)
 (030)
 (030)
 (193)
A502
07
1200
00
 (013)
1210
01H
1200
02H
A502
07
1200
02H
A502
15
 (040)
 KEEP 120000H
↑MOV #000A D00000
↑MOV #0002 D00001
↑MOV  #0400 D00002
↑MOV  #0705  D00003
↑MOV #0064 D00004
↑XFER  #0010  I0000  D00010
↑SEND D00010  D00020 D00000
 DIFU  120001H
↑MOV #0010 D00005
↑MOV #0003 D00006
↑MOV #2000 D00007
↑MOV #0705 D00008
↑MOV #0000 D00009
↑RECV  A100  2000  D00005
 DIFU 120003H
↑XFER  #0016  2000  D00040
1200
02H
03H
1200
A502
15
1200
00H
The transmission program will run when I000000 is ON, 
provided that the Network Instruction Enabled Flag for 
port 7 is ON and the RECV instruction has not been 
executed.
CIO 120000H remains ON while the SEND instruction 
is being executed, and it turns OFF when the execution 
of the instruction has been completed.
Word Content Meaning
D00000 00  0A  No. of send words: 10H
D00002 04  00  Destination node address: 4
    Destination unit address: 0
D00003 07  05  Response required
        Communications port no.: 7
        Number of retries: 5
The 10-word data starting from I0000 is stored in 
D00010 and following words.
Transmission error display
The reception program will run when I000001 is ON, 
provided that the Network Instruction Enabled Flag for 
port 7 is ON and the SEND instruction has not been 
executed.
CIO 120002H remains ON while the RECV instruction 
is being executed, and it turns OFF when the execution 
of the instruction has been completed.
Word Content Meaning
D00005  00  10  Number of receive words: 16H
D00006  00  03  Destination network address: 3
D00007  20  00  Destination node address: 32
      Destination Unit address: 0
D00008 07 05  Response required
      Communications port no.: 7
      Number of retries: 5
D00009  00  00  Response monitor time: Default 
Reception error display
Reception data processing
When the data is received without an error, the 16-word 
data received at CIO 2000 and following words is 
stored in D00040 and following words on the same PLC.
Transfers 10 words of data from the source node (D00010) 
to the PLC (from D00020 onwards) at network address 2, 
node no. 4, unit address 0.
Creates reset input.
Transfers 16 words of data (from A100 onwards) from 
the PLC at network address 3, node no. 32, unit address 
0, to words 2000 onwards.
Creates reset input.
D00001 00  02  Destination network address: 2
D00004 00  64  Response monitor time: 10 s