User's Manual
2.2.2. Signal functions
<Master unit to Slave unit>
Signal Name Description
OD0-0 to 7
OD1-0 to 7
OD2-0 to 7
OD3-0 to 7
Data output Output write data to the ID tag
ADDR0 to 15 Address
Specify start address for reading or writing.
Setting range:
0000H to FFFFH
LEN0 to 4 Data length READ, WRITE; specify the data length by the number of bytes
Setting range: 1H to 4H
DATA FILLI; specify the data length by the number of blocks
Setting range: 0H to FH
CMD0 to 3 Command
Specify the executing command
0000B Data read
0001B Data write
0010B Bit set
0011B Bit clear
0100B Data fill
1111B Noise measurement
Trigger mode When this signal is “1", FL REMOTE ID begins the communication
with the ID tag
TRG/~INHIBIT Trigger input/~Inhibit
Input
Auto mode When this signal is “0", FL REMOTE ID stops the communication
with the ID tag
HISPD High-speed Data
Transmission setting
“0” Normal mode
“1” High speed mode
VERIFY Write verification “0” With write verification
“1” Without write verification
WR PROTECT Write protection
function disable
“0” Enabled
“1” Disabled
OUTPUT TIME Output time setting “0” 100ms
“1” 500ms
<Slave unit to Master unit>
Signal Name Description
ID0-0 to 7
ID1-0 to 7
ID2-0 to 7
ID3-0 to 7
Data input Input read data from the ID tag
RUN RUN Turns “1” when FL REMOTE ID is operating normally and the communications are possible
with the plc
BUSY BUSY Output when a tag communications continues
NORM Normal output Output when communications with the ID tag are completed normally
ERR0 Error 0 output Output when communications with the ID tag are not completed normally
ERR1 Error 1 output Output when the command is illegal
ERR2 Error 2 output Output in the mode error
ERR3 Error 3 output Output when FL REMOTE ID is inoperative
ERR_SUB0 Error sub 0 No tag error
ERR_SUB1 Error sub 1 ID tag communication error
ERR_SUB2 Error sub 2 ID tag address error
ERR_SUB3 Error sub 3 Write protect error
ERR_SUB4 Error sub 4 Verification error
ERR_SUB5 Error sub 5 System error
ERR_SUB6 Error sub 6 System error