Section 4 DeviceNet Remote ID Controller
Section 4
Installation, Connections, and Wiring
Power Supply Connector
Use the enclosed connector. The user must provide the cable.
1. Attach the crimp terminals to the sections of the cable where the
sheath has been stripped.
2. Make sure the connector is facing the right direction and insert
each crimp terminal into the correct connector hole.
3. Once all of the cables have been connected to the connector,
attach the connector to the DeviceNet Remote ID Controller.
Align the cable connector with the connector on the DeviceNet Remote ID
Controller. Hold the connector body and push the connector firmly into place.
Removing the Connector
Remove the connector by pressing in on the lock on the cable connector to release the lock and pulling the connector
straight out. If the connector is difficult to remove, press on the DeviceNet Remote ID Controller while pulling on the
connector.
Do not connect cables to the connector after attaching the connector to the DeviceNet Remote ID Controller.
Use the recommended Power Supply (S8VS-03024, OMRON).
Brand Model Note
Cable Power line --- --- 1.0 mm
2
(equivalent to AWG18)
Connector
Phoenix Contact
FKC2.5/3-ST-5.08-RF ---
Crimp
Terminal
When one line is
connected to one
terminal
AI1-10RD
---
When two lines are
connected to one
terminal
AI-TWIN2 × 1-10RD
---
Crimping Tool CRIMPFOX UD6 ---