Section 6 Reference Data
RFID System
User's Manual
Section 6
Appendices
Multi-vendor Use
Connecting a Non-OMRON Configurator
This section describes how to connect OMRON Slaves to a non-OMRON Master.
Do not perform communications with a bit strobe connection for Slaves that have outputs. DeviceNet
I/O communications have multiple connection types, such as poll and bit strobe, but for DeviceNet
specifications, bit strobe connections are used for inputs only. Following these specifications, OMRON
Master Units communicate with output Slaves by using a poll connection.
Some non-OMRON Masters perform communications with output units by using a bit strobe
connection. Check the specifications before performing connections when connecting with a non-
OMRON Master.
When connecting an OMRON Slave to a non-OMRON Master, it is necessary to install the OMRON
Slave's EDS file in the non-OMRON Configurator, and set the Slave data in the Master. (Some non-
OMRON Masters can be connected with performing this setting.) In addition to enabling connection to
non-OMRON Masters, installing the EDS file in the Configurator also enables setting specific
parameters for each Slave by using the Configurator.
If the EDS file cannot be obtained or the non-OMRON Configurator does not support EDS files, you must directly input
the connection type and the data size.
Refer to the following devices profiles if more detailed DeviceNet specifications for Slaves are required
when registering the scan list.
Device Profiles
General data Applicable DeviceNet
specifications
Volume 1 Edition 3.1
Volume 3 Edition 1.3
Vendor name OMRON Corporation Vendor ID = 47
Device profile name Slave: Generic Profile number = 0
Product catalog number Manual number
Product revision 2.1
Physical
conformance
data
Network power consumption 24 VDC, 40 mA max.
Connector type Open flag
Physical layer insulation Yes
Support indicator Module
Network
MAC ID setting Set with software or rotary switches (software setting numbers 64 to 99)
Default MAC ID 0
Transmission baud rate setting No (baud rate recognized automatically)
Supported transmission baud rates 125, 250, or 500 kbps
Communications
data
Predefined Master/Slave
connection set
Group 2 only server
Dynamic connection support
(UCOMM)
No
Explicit message fragmentation
support
Ye s