5-8 Controller Control Command
5-22
5-8-6 Parameter Setting (SP)
Operates the parameters used in the controller from a host device.
Process code
(High order digit)
Specifies a type of process to parameter.
"0": Change
"1": Read
"9": Initialize (set to a default value)
Process code
(Low order digit)
Specifies a type of parameter.
"1": Character interval monitoring time
"2": Response Ready time
"3": Communication restriction time setting
Parameter data
(only when changing)
Data No. Available value
"1" Specifies four decimal digits. 0 to 9999 (ms)
"2" Specifies two decimal digits. 0 to 99 (ms)
"3" Specifies two decimal digits. 01 to 99 (x 10 ms). For "00", nothing is
specified.
<Command>
Command code
"SP"
Process code
Parameter data
(only when changing)
<Response>
Command
code
"SP"
Termination
code
Retrans-
mission
flag
Status
flag
Parameter data
(only when changing)