3-1 Controller
3-11
• Crimp terminal for terminal
M3 self-up screws are used for the terminal.
For a crimp terminal, use the terminal below.
Tightening torque should be approximately 0.6 N•m.
3-1-6-3 Wiring Output Signal
• Crimp terminal for terminal
M3 self-up screws are used for the terminal.
For a crimp terminal, use the terminal below.
Tightening torque should be approximately 0.6 N•m.
Correct Usage
Take care that the input voltage does not exceed the a maximum impressed voltage (26.4 V). Otherwise, a trouble may
occur in devices.
(For M3)
DC Power
Supply
Relay
External
I/O Unit
(For M3)