User Manual

Table Of Contents
3-1 Controller
3-10
3-1-6-1 Wiring Power Supply and Grounding Cable
M3 self-up screws are used for the power supply and ground terminal. For a crimp terminal, use any of terminals below. Tightening
torque should be approximately 0.6 N•m.
Applicable crimp terminal
Recommendable DC power supply (small-sized) (OMRON)
* Rated power consumption of the controller is 24VDC and 0.2 A (7 W). Decide the capacity taking into consideration inrush current
(approximately 5 A).
3-1-6-2 Wiring Reset Signal
Manufacturer Model Applicable Wire Type
Japan Solderless
Ter mi nal
1.25-N3A AWG24 to
AWG16
Fork
Japan Solderless
Ter mi nal
1.25-Y3A
Model Output Capacity Input Voltage
S82K-03024 24 VDC 1.3 A 100/200 VAC
S82J-0224 24 VDC 1.1 A 100 VAC
(Example of Wiring)
Grounding of Class D
+24 VDC
Reset Input
24 VDC
(For M3)