3-1 Controller
3-4
3-1-1-5 Setting a Dip Switch
SW3
SW3-1: Input function change
SW3-2: Operation mode
SW3-3: Verification at writing
SW3-4: Protocol designation
SW3-1 Description
ON Functions as trigger input.
OFF Functions as reset input.
SW3-2 Description
ON Starts in the Self-Execution mode when the power supply turns ON.
OFF Starts in the Command Execution mode when the power supply turns ON.
SW3-3 Description
ON Enables verification at a write command.
OFF Disables verification at a write command.
SW3-4 Description
ON Uses the 1:N protocol.
OFF Uses the 1:1 protocol.
Correct Usage
Set SW3-5, SW3-6, SW3-7 and SW3-8 to OFF always. Otherwise, any operation cannot be guaranteed.