Section 2 INSTALLATION & CONNECTION
ZFV-C
User’s Manual
Section 2
Amplifier Unit
Timing Charts
The following shows the timing charts when communication is performed with external
devices.
Measurement
Continuous measurement
Measurement is performed continuously for the duration that the TRIG signal is ON.
The measurement result is updated, and output to external devices at each measure-
ment cycle.
Synchronous measurement
Measurement is performed only once in synchronous with the change in TRIG signal
state from OFF to ON, and the result is output.
The minimum ON time width of the TRIG signal is 1 ms.
The OUTPUT signal is held until the measurement result is updated.
Note, however, when one-shot output is set, the OUTPUT signal is held for the preset
time.
One-shot Output p.107
Tou t
TRIG
OUTPUT
ENABLE
OFF
ON
OFF
ON
OFF
ON
Tout: Measurement cycle
The measurement cycle changes
depending on the setting.
Tou t
TRIG
OUTPUT
ENABLE
OFF
ON
OFF
ON
OFF
ON
Tout: Measurement time.
The measurement time changes
depending on the setting.