Datasheet

ZEN V2 Units
23
8. Display Settings (Only for Standard LCD-type, Economy-type, and Communications-type
CPU Units)
Note: 1. When L0 or L1 are selected to disable the display function screen, the display function screen will not be displayed automatically. Use
operation buttons to move to the display function screen.
2. When L2 or L3 are selected, the ZEN switches to the display function screen if the display function is enabled and the specified data is
displayed. The Main Screen will no longer be displayed. To display the Main Screen, change the CPU Unit to STOP mode.
9. Analog Comparator Operation
10. Timer/Counter Comparator Operation
11. 8-digit Counter Comparator Operation
Backlight/display
function screen
switching
L0: No backlight; No switching to display function screen (See note 1.)
L1: Backlight; No switching to display function screen (See note 1.)
L2: No backlight; Switching to display function screen (See note 2.)
L3: Backlight; Switching to display function screen (See note 2.)
Display start
position
X (digit): 00 to 11
Y (line): 0 to 3
Display object CHR Characters (Up to 12 characters - English, numerals, symbols)
DAT Month/day (5 digits @@/@@)
CLK hour/minute (5 digits @@:@@)
I4 to I5 Analog-converted value (4 digits @@:@)
T0 to Tf Timer present value (5 digits @@.@@)
#0 to #7 Holding timer present value (5 digits @@.@@)
C0 to Cf Counter present value (4 digits @@@@)
F0 8-digit counter present value(8 digits @@@@@@@@)
Monitoring A: Can read settings during operation.
D: Cannot read settings during operation.
X00 X11
Y0 to Y3
10.5
10.0
5.2
00.0
0.0 10.0 V
Input voltage
10.5 V
Setting
Analog
comparator bit
Analog
comparator bit
10.0
00.0
Analog input 1
Analog input 2
Converted value
Example 1
(When comparison shows analog input
1 5.2 V)
Example 2
(When comparison shows analog input 1 is
analog input 2)
Comparator
bit
Comparator
bit
C1 present value
C2 present value
#0 present value
Setting
12 min 34 s
0
Example 1
(When comparison setting is holding
timer #0 12 min 34 s)
Example 2
(When comparison setting is counter 1 (C1)
counter 2 (C2))
8-digit counter
comparator
bit
0
12000000
F0 present value
Wh
en compar
i
son sett
i
ng
i
s
8-digit counter F0 12000000