Datasheet

H3YN-@-B
26
Life-test Curve (Reference Value)
500
100
50
20
500
100
50
20
500
100
50
20
500
100
50
20
500
100
50
10
6
H3YN-2-B/-21-B
H3YN-4-B/-41-B
H3YN-4-Z-B/-41-Z-B
Switching operations (x 10
4
)
Load current (A)
Switching operations (x 10
4
)
Load current (A)
Switching operations (x 10
4
)
Load current (A)
Switching operations (x 10
4
)
Load current (A)
Switching operations (x 10
4
)
Load current (A)
250 VAC, resistive load
250 VAC, cosφ = 1
24 VDC, cosφ = 1
Reference: A maximum current of 0.6 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases, a
life of 100,000 operations can be expected.
The minimum applicable load is 1 mA at 5 VDC (P reference value)
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
250 VAC, cosφ = 1
24 VDC, cosφ = 1
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases, a
life of 100,000 operations can be expected.
The minimum applicable load is 1 mA at 1 VDC (P reference value)
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
24 VDC,
resistive load
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases, a
life of 100,000 operations can be expected.
The minimum applicable load is 0.1 mA at 1 VDC (P reference value