Datasheet
XW5T
11
Grounding Terminal blocks Multi conductor terminals
Note: If you use a Grounding Terminal Block, use a DIN Track for grounding.
*1. For the applicable wire ranges, refer to page 17 for solid and stranded wires and to page 19 for ferrules.
*2. You can also use 1.25 mm
2
wires if you use 1.0 mm
2
ferrules. However, if you do, care is required in the finished outer shape of the wires.
Model XW5G-P1.5-1.2-1 XW5G-P2.5-1.2-1 XW5G-P4.0-1.2-1
Appearance and internal
wiring
1 tier, 1:2
1 tier, 1:2
1 tier, 1:2
Applicable wire sizes*1
NOMINAL CROSS
SECTION
1.0 mm
2
(1.25 mm
2
)*2 2.5 mm
2
4.0 mm
2
Minimum conductor
cross section solid
0.14 mm
2
0.14 mm
2
0.2 mm
2
Maximum conductor
cross section solid
1.5 mm
2
4.0 mm
2
6.0 mm
2
Minimum conductor
cross section fine
stranded
0.08 mm
2
0.14 mm
2
0.2 mm
2
Maximum conductor
cross section fine
stranded
1.5 mm
2
2.5 mm
2
4.0 mm
2
Minimum conductor
cross section (flex.,
stranded) with ferrule
with Plastic sleeve
0.14 mm
2
0.14 mm
2
0.25 mm
2
Maximum conductor
cross section (flex.,
stranded) with ferrule
with Plastic sleeve
1.0 mm
2
(1.25 mm
2
)*2 2.5 mm
2
4.0 mm
2
Dimensions 3.5 × 54.1 × 30.5 5.2 × 60.5 × 35.3 6.2 × 66.5 × 35.3
IEC rated voltage 500 V 800 V
UL rated voltage 600 V 600 V
Dielectric strength
1,890 VAC for 1 min
(leakage current: 1 mA max.)
2,000 VAC for 1 min
(leakage current: 1 mA max.)
End Cover XW5E-P1.5-1.2-1 XW5E-P2.5-1.2-1 XW5E-P4.0-1.2-1
Special tool XW4Z-00B
Applicable nameplates
XW5Z-P1.5LB@ or commercially available
nameplate with 9.5 mm width and 0.5 mm
thickness
XW5Z-P2.5LB@ or commercially available
nameplate with 9.5 mm width and 0.5 mm
thickness
XW5Z-P4.0LB@ or commercially available
nameplate with 9.5 mm width and 0.5 mm
thickness
Applicable Short Bars
XW5S-P1.5-@
(@: Poles = 2, 3, 4, 5 or 10)
XW5S-P2.5-@
(@: Poles = 2, 3, 4, 5 or 10)
XW5S-P4.0-@
(@: Poles = 2, 3, 4, 5 or 10)