Approved Standards
Approved Standard Ratings
UL/cUL (UL508, CSA C22.2 No.14)
A600 Authentication conditions
B600 Authentication conditions
C300 Authentication conditions
A300 Authentication conditions
General-purpose/ Environment-resistant/ Spatter-prevention Switches
Agency Standard File No. Approved models
UL
UL508
Contact your OMRON representative for information Contact your OMRON representative for information
CSA C22.2 No.14
V Rheinland EN60947-5-1
CCC (CQC) GB14048.5
Specifications
Approved Standards
Indicator Sensor I/O connectors Item
No indicator
No Connector
Basic Switches
A600
1 A, 125 VDC
High-sensitivity or high-precision
B600
0.5 A, 125 VDC
Pre-wired Connector (AC) Basic, high-sensitivity, or high-precision
C300
3 A, 250 VAC
Pre-wired Connector (DC)
Direct-wired Connector (DC)
Basic Switches 1 A, 125 VDC
High-sensitivity or high-precision 0.5 A, 125 VDC
Neon lamp
No Connector
Basic Switches
A300
10 A, 250 VAC
High-sensitivity or high-precision
B300
5 A, 250 VAC
Pre-wired Connector (AC) Basic, high-sensitivity, or high-precision
C300
3 A, 250 VAC
LED
No Connector
Basic Switches
A150
10 A, 115 VAC
1 A, 115 VDC
High-sensitivity or high-precision
B150
5 A, 115 VAC
0.5 A, 115 VDC
Pre-wired Connector (AC) Basic, high-sensitivity, or high-precision
C150
3 A, 115 VAC
Pre-wired Connector (DC)
Direct-wired Connector (DC)
Basic Switches 1 A, 115 VDC
High-sensitivity or high-precision 0.5 A, 115 VDC
Rated voltage Energizing current
Current (A) Volt-ampere (VA)
Make Break Make Break
120 VAC
240 VAC
480 VAC
600 VAC
10 A
60
30
15
12
6
3
1.5
1.2
7,200 720
Rated voltage Energizing current
Current (A) Volt-ampere (VA)
Make Break Make Break
120 VAC
240 VAC
480 VAC
600 VAC
5 A
30
15
7.5
6
3
1.5
0.75
0.6
3,600 360
Rated voltage Energizing current
Current (A) Volt-ampere (VA)
Make Break Make Break
120 VAC
240 VAC
2.5 A
15
7.5
1.5
0.75
1,800 180
Rated voltage Energizing current
Current (A) Volt-ampere (VA)
Make Break Make Break
120 VAC
240 VAC
10 A
60
30
6
3
7,200 720