Datasheet

S8VK-X
3
Ratings, Characteristics, and Functions
* Refer to Definitions of the Terms Under Ratings, Characteristics, and Functions on page 6.
Power rating 30 W 60 W
Rated output voltage 5 V 12 V 24 V
Item Indication monitor None None None
Efficiency *
115 VAC input 78% typ. 85% typ. 85% typ.
230 VAC input 77% typ. 86% typ. 86% typ.
Input
conditions
Voltage range * Single-phase, 85 to 264 VAC, 90 to 350 VDC, 265 to 300 VAC (1 second)
Frequency * 50/60 Hz (47 to 450 Hz)
Input current *
115 VAC input 0.53 A typ. 0.99 A typ. 1.1 A typ.
230 VAC input 0.32 A typ. 0.61 A typ. 0.67 A typ.
Power factor ---
Leakage current *
115 VAC input 0.5 mA max.
230 VAC input 1 mA max.
Inrush current *
115 VAC input 16 A typ.
230 VAC input 32 A typ.
Output
characteristics
Rated output current 5 A 4.5 A 2.5 A
Rated output power 25 W 54 W 60 W
Maximum boost current 6 A 5.4 A 3 A
Voltage adjustment range * 4.5 to 5.8V (with V. ADJ) 10.8 to 14 V (with V. ADJ) 21.6 to 28 V (with V. ADJ)
Ripple noise voltage
*
100 to 240 VAC input
130 mVp-p max.
at 20 MHz of bandwidth
120 mVp-p max.
at 20 MHz of bandwidth
110 mVp-p max.
at 20 MHz of bandwidth
Input variation influence * 0.5% max.
Load variation influence * 1.5% max.
Temperature
variation influence
100 to 240 VAC input 0.05%/°C max.
Start up time *
115 VAC input 1000 ms max. 1000 ms max. 1000 ms max.
230 VAC input 1000 ms max. 1000 ms max. 1000 ms max.
Hold time *
115 VAC input 45 ms typ. 20 ms typ. 20 ms typ.
230 VAC input 240 ms typ. 120 ms typ. 110 ms typ.
Additional
functions
Overload protection
Yes, automatic reset, intermittent operation type, Refer to Overload Protection on page 8 for details.
Overvoltage protection
Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn
on the input again), Refer to Overvoltage Protection on page 8 for details.
Series operation Yes (For up to two Power Supplies; external diodes required.)
Parallel operation Yes (For up to two Power Supplies), Refer to Parallel Operation on page 22 for details.
Output indicator Yes (LED: Green)
Alarm indicator Yes (LED: Red)
Indication monitor
Measurement and
display details
Refer to Communication and Indication Items on page 7 for details.
Main display None
Ethernet
communication
Measurement and
display details
Refer to Communication and Indication Items on page 7 for details.
Communication protocol
EtherNet/IP, Modbus TCP
Physical layer 100BASE-TX
Communication
specifications
Refer to Communication Specifications on page 8 for details.
Insulation
Withstand voltage
3.0 kVAC for 1 min. (between all input terminals and output terminals, all EtherNet/IP ports),
current cutoff 20 mA
2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA
1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 30 mA
0.5 kVAC for 1 min. (between all output terminals and all EtherNet/IP ports), current cutoff 30 mA
Insulation resistance
100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC
100 MΩ min. (between all EtherNet/IP ports and all input terminals) at 500 VDC
Environment
Ambient operating temperature *
-40 to 70°C (Derating is required according to the temperature. Refer to Engineering Data)
(with no condensation or icing)
Storage temperature -40 to 85°C (with no condensation or icing)
Ambient operating humidity 95% max. (Storage humidity: 95% max.)
Vibration resistance 10 to 55 Hz, maximum 5 G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions
Shock resistance 150 m/s
2
, 3 times each in ±X, ±Y, ±Z directions
Reliability
MTBF * 160,000 hrs typ.
Life expectancy * 10 years min.
Construction
Weight 250 g max. 250 g max. 250 g max.
Cooling fan No
Degree of protection IP20 by EN/IEC 60529