Datasheet

S8VK
Series line-up
8
Ordering information
S8VK-G series
S8VK-C series
S8VK-R series
Specifications
S8VK series
Type Power ratings Input voltage Output voltage Output current Size (W × H × D) [mm] Order code
Power supply
Single phase
15 W 100 to 240 VAC
Allowable range:
85 to 264 VAC,
90 to 350 VDC,
2 phases less than 240 VAC
5V 3A 22.5 × 90 × 90 S8VK-G01505
12 V 1.2 A S8VK-G01512
24 V 0.65 A S8VK-G01524
30 W 5V 5A 32 × 90 × 90 S8VK-G03005
12 V 2.5 A S8VK-G03012
24 V 1.3 A S8VK-G03024
60 W 12 V 4.5 A 32 × 90 × 110 S8VK-G06012
24 V 2.5 A S8VK-G06024
120 W 24 V 5A 40 × 125 × 113 S8VK-G12024
240 W 24 V 10 A 60 × 125 × 140 S8VK-G24024
48 V 5A S8VK-G24048
480 W 24 V 20 A 95 × 125 × 140 S8VK-G48024
48 V 10 A S8VK-G48048
Type Power ratings Input voltage Output voltage Output current Size (W × H × D) [mm] Order code
Power supply
Single phase
60 W Single phase
100 to 240 VAC
(Allowable range:
85 to 264 VAC)
24 V 2.5 A 32 × 90 × 110 S8VK-C06024
120 W 24 V 5A 40 × 125 × 113 S8VK-C12024
240 W 24 V 10 A 60 × 125 × 140 S8VK-C24024
480 W 24 V 20 A 95 × 125 × 140 S8VK-C48024
Type Input voltage Output current Size (W × H × D) [mm] Order code
Redundancy Module 5 to 30 VDC 10 A 32 × 90 × 110 S8VK-R10
12 to 60 VDC 20 A 40 × 125 × 113 S8VK-R20
Type S8VK-G
Efficiency (Ave) 90%
Input Rated Input Voltage 100 to 240 VAC
Allowable range 85 to 264 VAC, 90 to 350 VDC
2 phases less than 240 VAC
Harmonic current emissions Conforms to EN61000-3-2
Leakage current at 200 VAC 1 mA max
Inrush current at 230 VAC 40 A max
Output Voltage adjustment range –10% to 15% (with V.ADJ)
Ripple 2.0% (p-p) max. (at rated input/output voltage)
Input variation influence 0.5% max. (at 85 to 264 VAC input, 100% load)
Load variation Influence 3.0% max. (5 V), 2.0% max. (12 V), 1.5% max. (24, 48 V), at 0% to 100% load
Temperature variation influence 0.05%/°C max.
Start up time 1,000 ms max
Hold time 20 ms min
Additional functions Overload protection Yes, 130% of rated current type
Power Boost 120% of rated current * Refer to “Power Boost function”
Overvoltage protection Yes
Parallel operation Possible for up to 2 units
Series operation Possible for up to 2 units