Adjusting Output Voltage for Parallel
Operation
The Blocks are factory-set to the rated output voltage. When adjust-
ing voltages, set the same values for Blocks with V.ADJ before linking
them together. Adjust the set values within the limits given in the fol-
lowing table.
Do not adjust voltages after Blocks are linked together. The output
voltage may become unstable.
Inrush Current
The inrush current per Basic Block is 25 A max. at 100 VAC and 50 A
max. at 200 VAC. When N Blocks are linked together, the inrush cur-
rent will be equal to N times that for 1 Basic Block. Be sure to use a
fuse with the appropriate fusing characteristics or a breaker with the
appropriate tripping characteristics.
Leakage Current
The leakage current per Basic Block is 0.35 mA at 100 VAC and
0.7 mA at 240 VAC. When N Blocks are linked together, the leakage
current will be equal to N times that for 1 Basic Block.
Mounting
Mounting Direction
Use standard mounting only. Using any other mounting method will
prevent proper hear dissipation and may result in deterioration or
damage of internal elements.
Model number Difference between output
voltages
S8TS-06024@ 0.24 V max.
S8TS-03012@ 0.12 V max.
L
N
L
N
L
N
L
N
S8T
-BUS02
S8T
-BUS02
Series Operation ± Output
Load Load Load Load Load Load
24/12-V models 5-V models 24/12-V models 5-V models
Standard mounting Yes
Face-up mounting No
Other mounting methods No
Standard mounting
Face-up mounting